Installing the Indoor PI
Insert the PI into a slot on the auxiliary mounting bracket
and tighten the captive screws on the mounting ears.
Fix the floating nuts.
1
When you fix the floating nuts, allow a heat dissipation space of at least 25 mm
above and below the PI.
Floating
nut
Optional: Installing the PI in a 19-Inch Cabinet
Mounting hole
2.0
±
0.2 N·m
M6
1.4
±
0.14 N·m
M4
Attach the PGND cable to a
ground point on a cabinet
column or to an indoor
ground bar.
Install the PGND cable with the
ground screw (M4).
Install the chassis in the cabinet.
2
Install the PGND cable.
3
ETSI
Mounting
ears
Before installing the chassis in an ETSI cabinet,
adjust the holes for installing mounting ears
based on the cabinet type.
3.0
±
0.3 N·m
M6
Optional: Installing the PI in an ETSI Cabinet
Install the ETSI mounting ears.
3
Floating
nut
Attach the PGND cable to a ground
point on a cabinet column or to an
indoor ground bar.
2.0
±
0.2 N·m
M6
Install the PGND cable with the
ground screw (M4).
Install the chassis in the cabinet.
2
Install the PGND cable.
4
Fix the floating nuts.
1
42/43 >>
Installation Reference
When you fix the floating nuts, allow a heat dissipation space of at least 25 mm
above and below the PI.
1.4
±
0.14 N·m
M4