3
Replacement Procedure
CA UTION
The low-voltage bushing shall be replaced in clear and windless weather to avoid
wind, sand or rain pollution of transformer oil.
NO TE
After all the materials are ready, repair the equipment.
3.1 Cut off the power supply of STS
3.2 Replacement procedure
3.3 Restore the power supply of STS
3.4 Observe the STS repair
3.1 Cut off the power supply of STS
Step 1 Switch off G2 cabinet circuit breaker, switch off G2 cabinet isolation switch and
switch on G2 cabinet earthing switch.
Step 2 Switch off the ACB of low-voltage cabinets LVA and LVB.
----End
3.2 Replacement Procedure
Step 1 Connect the oil storage bag, oil pump and flange with oil pipe, and fix the oil pipe
with throat hoop.
Smartkits
Guide to Transformer Low Voltage Bushing
Replacement (No Handhole Replacement)
3 Replacement Procedure
Issue 01 (2021-11-22)
Copyright © Huawei Digital Power Technologies Co.,
Ltd.
7