NO TE
1. Clean the position of the sealing ring of the low-voltage bushing and clamp the sealing
ring in the sealing groove.
2. Insert the low-voltage bushing into the hole, and take care to avoid shifting of the
sealing gasket.
3. Install the fixing steel plate and tighten the bolts. Tighten the bolts gradually in the
diagonal sequence to avoid directly locking a single bolt at a time.
Installation torque: 45 Nm.
Step 22 Lower the lid height to 3 cm.
Smartkits
Guide to Transformer Low Voltage Bushing
Replacement (No Handhole Replacement)
3 Replacement Procedure
Issue 01 (2021-11-22)
Copyright © Huawei Digital Power Technologies Co.,
Ltd.
25