NO TE
● After you restart the device, IP address allocation changes back to Manual. The IP
address is set to the IP address set previously.
● Ensure that the UPS IP address is unique on the network segment. Otherwise, the
WebUI display function may not function properly.
Table 5-10 System Settings
Item
Description
Default
Value
Value Range
Battery cabinet
quantity
Specifies the number of
battery cabinets connected in
parallel.
1
1–15
Charging mode
Mode 1 can meet the
requirements of most
customers.
Mode 2 meets the
requirements for charging
batteries immediately after
discharging is complete at a
high temperature.
Mode 1
Mode 1, Mode 2
Cell
undervoltage
protection
threshold (V)
You can adjust the EOD
threshold as required.
2.5
2.5–2.9
Battery
undervoltage
protection time
(h)
Maximum battery discharge
time.
48
24~3000
Table 5-11 Settings Wizard
Item
Description
Remarks
Language
English, Chinese
Set based on site
requirements.
Time
Date format, YYYY-MM-DD, time zone,
city, and time
Set based on site
requirements.
Network Param.
IP address allocation, IP address,
subnet mask, and gateway
Set based on site
requirements.
System Param.
Battery cabinet quantity, charging
mode, cell undervoltage protection
threshold, and battery undervoltage
protection time
Set based on site
requirements.