Item
Description
Default Value
Value Range
DO_2
Output dry
contact 2 function
setting for the
lithium battery
cabinet
None
● None
● Critical alarm
● Minor alarm
● Fire
extinguishing
started
● Battery temp.
abnormal
● Battery EOD
● Battery
undervoltage
DO_2 Action
Output dry
contact 2 action
setting for the
lithium battery
cabinet
Close
● Close
● Open
Table 5-15 Alarm Settings
Item
Description
Default
Value
Value
Range
Battery cabinet
EPO
Emergency power-off (EPO) is
performed only when this
parameter is set to Enable and
the EPO switch is triggered.
When the value is changed from
Disable to Enable, check that the
EPO cable is connected correctly.
Disable
Disable,
Enable
Copper bar
overtemperature
If this parameter is set to Enable,
an alarm is reported when the
copper bar is overheated.
Enable
Disable,
Enable
Fire extinguisher
cylinder pressure
abnormal
If this parameter is set to Enable,
an alarm is reported when the fire
extinguisher cylinder pressure is
abnormal.
Enable
Disable,
Enable
Battery
overcurrent
(discharge)
If this parameter is set to Disable,
no alarm is reported when battery
overcurrent occurs during
discharging.
If this parameter is set to Enable,
an alarm is reported when battery
overcurrent occurs during
discharging.
Disable
Disable,
Enable
SmartLi 2.0
User Manual
5 User Interface
Issue 09 (2022-01-30)
Copyright © Huawei Technologies Co., Ltd.
103