6.1 Connecting the Battery Supply
Prerequisites
●
Turn on the ready switch on the BCU.
●
Ensure that the UPS runs stably in normal mode and the rectifier in the
energy flow diagram is started.
Context
Table 6-1 Status of Indicators on the BCU
Status of Indicators on the BCU
Description
The green indicator blinks at 4 Hz (at
short intervals).
Status after the switch button is
pressed.
The green indicator blinks on for 1s
and off for 4s (intermittently).
The SmartLi circuit breaker cannot be
switched on, and the UPS cannot be
cold started.
The green indicator blinks at 10 Hz
(blinking at super short intervals), and
the red indicator is steady on.
The SmartLi circuit breaker can be
switched on, but the UPS cannot be
cold started.
The green indicator blinks at 1 Hz or is
steady on (blinking at long intervals).
The UPS can be cold started.
Procedure
Step 1 On the UPS LCD screen, set System Info > Settings > Battery Settings > Battery
Type to Lithium battery.