NO TE
● When the ambient temperature of the system is beyond the normal range, the power
backup capability may be unavailable or not reach the rated value.
● A battery module cannot be directly charged or discharged at a temperature below 0°C.
When the battery module temperature is below 0°C, it will turn off the charging and
discharge circuits.
● When a battery module is used in an environment below 0°C, the air conditioner needs
to be started for heating, and the battery module can be charged or discharged only
after the module temperature rises to 3°C or above.
Table 10-3 Safety and EMC
Item
Specifications
Safety
complianc
e
CE
EN 62619
EN 62040-1
CB
IEC 62619
IEC 62040-1
EMC
Conducted
emission (CE)
EN/IEC 62040-2
Radiated emission
(RE)
EN/IEC 62040-2
Low-frequency
signal interference
IEC 61000-2-2
Electrostatic
discharge immunity
IEC 61000-4-2
Conducted
susceptibility
EN/IEC 62040-2
EN/IEC 61000-4-6
Radiated
susceptibility
EN/IEC 62040-2
EN/IEC 61000-4-3
Electrical fast
transient (EFT)
EN/IEC 62040-2
IEC 61000-4-4
Surge protection
EN/IEC 62040-2
IEC 61000-4-5
Power frequency
magnetic field
IEC 61000-4-8
SmartLi 2.0
User Manual
10 Technical Specifications
Issue 09 (2022-01-30)
Copyright © Huawei Technologies Co., Ltd.