Table 3-4 Qualification standard for recharge
Lithium Battery
Model
Required
Recharge End
Voltage
Voltage
Requirement
After Staying in
Open-Circuit
State for 10
Minutes
Subsequent to
Recharge
Method for
Measuring
Battery Voltage
ESM-6440P1
≥ 66.6 V
≥ 64 V
· Use a voltmeter
to measure the
voltage between
the positive and
negative
terminals of the
battery.
· View the battery
voltage displayed
on the LCD.
NO TE
● If the battery is qualified after recharge, remove cables, place it in the original packing
case, and update the latest charge time and next recharge time on the recharge label of
the original packing case. The battery should be used as soon as possible.
● If the battery is not qualified after recharge, recharge it again. If the battery is still not
qualified, dispose of it.
----End
Recharge with a Battery Charger/Discharger
Step 1 Identify the battery module qualified for recharge.
Step 2 Install cables between the portable battery charger/discharger and the battery
module.
SmartLi 2.0
User Manual
3 Transportation and Storage
Issue 09 (2022-01-30)
Copyright © Huawei Technologies Co., Ltd.
34