NO TICE
● Keep the fire extinguisher cylinder upright.
● Ensure that the front of the pressure gauge faces the right side of the cabinet
(as shown in the figure) and that the cylinder does not interfere with the
battery trays and the rear cover of the cabinet.
Figure 4-3 Installing the fire extinguisher cylinder and dry contact cable
Step 8 Install the fire-trace tube.
NO TICE
Do not bend or twist the fire-trace tube or bind the tube using cable ties.
Otherwise, the extinguishant may leak.
1. Clamp the end of the fire-trace tube to the threaded nozzle using a pipe
holder or slip-proof gloves.
NO TICE
Hold the pipe holding device close to the end to avoid bending the tube
during pipe insertion.
SmartLi 2.0
User Manual
4 Installation
Issue 09 (2022-01-30)
Copyright © Huawei Technologies Co., Ltd.
45