Check that the value of the pressure gauge on the fire extinguisher cylinder is
within the allowable pressure range (1.6–1.8 MPa at 20°C) specified in
Step 8 Install the fire extinguisher cylinder in the lithium battery side cabinet.
1. Remove the front door panel from the lithium battery side cabinet.
2. Install the fire extinguisher cylinder.
NO TICE
– Keep the fire extinguisher cylinder upright.
– Ensure that the front of the pressure gauge faces the front door panel of
the cabinet, as shown in the figure.
Figure 4-14 Installing a fire extinguisher cylinder (one SmartLi cabinet and
one lithium battery side cabinet)
SmartLi 2.0
User Manual
4 Installation
Issue 09 (2022-01-30)
Copyright © Huawei Technologies Co., Ltd.
54