NO TICE
If two SmartLi cabinets and one lithium battery side cabinet are configured,
connect the fire-trace tube in the left SmartLi to the lower fire extinguisher
cylinder, and connect the fire-trace tube in the right SmartLi to the upper fire
extinguisher cylinder.
1. Clamp the end of the fire-trace tube to the threaded nozzle using a pipe
holder or slip-proof gloves.
NO TICE
Hold the pipe holding device close to the end to avoid bending the tube
during pipe insertion.
Figure 4-24 Installing a fire-trace tube
(1) If the pipe holding device is slip-proof gloves, install the fire-trace tube using slip-proof
gloves.
2. Tighten the connection nut to 7 N·m using an adjustable torque wrench.
Step 8 Remove the valve positioning kit, open the valve, reinstall the positioning kit, and
secure it.
NO TICE
Slowly open the valve. To avoid unexpected blowout, do not quickly open the
valve.
SmartLi 2.0
User Manual
4 Installation
Issue 09 (2022-01-30)
Copyright © Huawei Technologies Co., Ltd.
62