Figure 4-52 Installing cables (BBB box, without neutral wires)
Figure 4-53 Installing cables (BBB box, with neutral wires)
NO TICE
● The following figure shows how to connect a communications cable between
the SmartLi and the integrated UPS.
–
W1 and W2, and W3 and W4 respectively use a group of twisted-pair
cables, and other redundant core wires are cut off.
–
The cable colors in the figure are for reference only. The actual cable colors
may vary.
● Communications cables between the SmartLi and other UPS models are
connected using standard network cables.
● If more than eight SmartLi cabinets are connected in parallel, a maximum of
four 15 m parallel communications cables are supported.