Step 6
Route the AC output power cable through the locking cap and then the
AC OUTPUT
connector at the inverter bottom.
Step 7
Connect the SUN2000-33KTL AC output wires to pins L1, L2, L3, and N of the AC terminal
block and tighten the screws to a torque of 4 N·m using a 10 mm socket wrench. Connect the
SUN2000-30KTL-A or SUN2000-40KTL AC output wires to pins L1, L2, and L3 of the AC
terminal block and tighten the screws to a torque of 8 N·m using a 13 mm socket wrench.
To connect a ground cable to the ground point in the maintenance compartment, tighten the
ground screw to a torque of 4 N·m using an M6 torque screwdriver.
Ensure that the AC output power cable is securely connected. Otherwise, the inverter may fail
to run or the terminal block may be damaged after the device operates.
Figure 5-11
Connecting the SUN2000-33KTL AC output cable (excluding the ground cable)