Alarm
ID
Alarm
Name
Alarm
Severity
Cause
Measures
2063
Cabinet
Overte
mperat
ure
Major
Cause ID = 1
1. The SUN2000 is installed in a
place with poor ventilation.
2. The ambient temperature
exceeds the upper threshold.
3. The SUN2000 is not working
properly.
1. Check the ventilation and
ambient temperature at
the SUN2000 installation
position. If the ventilation
is poor or the ambient
temperature exceeds the
upper threshold, improve
the ventilation and heat
dissipation.
2. If the ventilation and
ambient temperature both
meet requirements, contact
Huawei technical support.
2064
Device
Fault
Major
Cause ID = 1-15
An unrecoverable fault occurs on a
circuit inside the SUN2000.
Turn off the AC output switch
and DC input switch, and then
turn them on after 5 minutes.
If the fault persists, contact
Huawei technical support.
NOTICE
Cause ID = 1: Perform the
preceding operations when the
PV string current is less than 1 A.
2065
Upgrad
e Failed
Minor
Cause ID = 1-5
The upgrade ends abnormally.
1. Perform an upgrade again.
2. If the upgrade fails several
times, contact your dealer.
2066
License
Expired
Warning
Cause ID = 1
1. The privilege certificate has
entered the grace period.
2. The privilege feature will be
invalid soon.
1. Apply for a new certificate.
2. Load the new certificate.
61440
Faulty
Monito
ring
Unit
Minor
Cause ID = 1
1. The flash memory is
insufficient.
2. The flash memory has bad
sectors.
Turn off the AC output switch
and DC input switch, and then
turn them on after 15
minutes. If the fault persists,
replace the monitoring board
or contact Huawei technical
support.
SUN2000-(50KTL, 60KTL, 65KTL)-M0
User Manual
8 Maintenance
Issue 06 (2020-07-07)
Copyright © Huawei Technologies Co., Ltd.
101