Item
SUN2000-50KTL-
M0
SUN2000-60KTL-
M0
SUN2000-65KTL-
M0
PV string
fault
detection
Supported
DC surge
protection
Type II
AC surge
protection
Type II
Insulation
resistance
detection
Supported
Residual
current
monitoring
unit (RCMU)
Supported
Overvoltage
category
PV II/AC III
Built-in PID
repair
c
Optional
Optional
Not supported
Note c: When the SUN2000 is disconnected from the grid and stops working,
the built-in PID can achieve the PV– positive offset of the PV module. (PV–
positive offset refers to raising the voltage between PV– and the ground to
above 0 V through voltage compensation.) When designing a power plant,
confirm with the PV module manufacturer that the anti-PID voltage
compensation direction of the PV module is the same as the direction of the
PV– positive offset. Otherwise, PV modules may be damaged.
CA UTION
For the SUN2000 that supports built-in PID repair, when Built-in PID running
mode is set to Repair, there is repair voltage between PV modules and the ground
at night. If you need to maintain PV modules at night, power off the SUN2000 to
avoid electric shocks.
Display and Communication
Item
SUN2000-50KTL-
M0
SUN2000-60KTL-
M0
SUN2000-65KTL-
M0
Display
LED, Bluetooth app, USB data cable+app, WLAN module
+app
SUN2000-(50KTL, 60KTL, 65KTL)-M0
User Manual
10 Technical Specifications
Issue 06 (2020-07-07)