Model
Recommended Overcurrent
Protection Device Specifications
SUN2000-50KTL-M0
125 A
SUN2000-60KTL-M0
125 A
SUN2000-65KTL-M0
125 A
WARNING
Do not connect loads between the SUN2000 and the AC switch.
The SUN2000 is integrated with a comprehensive residual current monitoring unit
(RCMU) to distinguish fault current from residual current. Upon detecting that the
residual current exceeds the threshold, the SUN2000 immediately disconnects
from the power grid.
NO TE
● If an AC switch that can detect residual current is installed outside the SUN2000-50KTL-
M0, the residual current value to trigger the switch should be greater than 550 mA.
● If an AC switch that can detect residual current is installed outside the SUN2000-60KTL-
M0, the residual current value to trigger the switch should be greater than 660 mA.
● If an AC switch that can detect residual current is installed outside the SUN2000-65KTL-
M0, the residual current value to trigger the switch should be greater than 720 mA.
Wiring Precautions
NO TICE
Ensure that the SUN2000 PE cable is securely connected. Otherwise the repair of
the built-in PID would be affected.
●
The ground point on the enclosure is preferred to connect to the PE cable for
the SUN2000.
●
The ground point in the maintenance compartment is mainly used for
connecting to the ground cable included in the multi-core AC power cable.
●
There are two ground points on the enclosure and you only need either of
them.
●
It is recommended that the ground cable be connected to a nearby ground
point. For a system with multiple SUN2000s connected in parallel, connect the
ground points of all SUN2000s to ensure equipotential connections to ground
cables.
Cable Specifications
●
For the SUN2000-50KTL/60KTL-M0:
SUN2000-(50KTL, 60KTL, 65KTL)-M0
User Manual
5 Electrical Connections
Issue 06 (2020-07-07)
Copyright © Huawei Technologies Co., Ltd.
40