Figure 5-11 Four-core cable (excluding the ground cable but including the neutral
wire)
Figure 5-12 Five-core cable (including the ground cable and neutral wire)
Step 4 Crimp an OT terminal.
Step 5 Land the AC output power cable in the terminal block, and tighten the nuts with a
torque wrench that has an extension rod.
NO TICE
● Ensure that AC terminations provide firm and solid electrical connections.
Failing to do so may cause SUN2000 malfunction and damage to its terminal
block, even starting thermal events. Any SUN2000 damaged due to weak
termination will result in revocation of product warranty.
● When connecting a PE cable, secure the screws using a socket wrench with an
extension wrench longer than 200 mm.
● Sufficient slack should be provided in the PE cable to ensure that the last cable
bearing the force is the PE cable when the AC output power cable bears pulling
force due to force majeure.