Parameter List
Parameter
Description
Remarks
MPPT multi-peak
scanning
When the SUN2000 is used in
scenarios where PV strings are
obviously shaded, enable this
function. Then the SUN2000 will
perform MPPT scanning at regular
intervals to locate the maximum
power.
The scanning interval is set by
MPPT multi-peak scanning
interval.
MPPT multi-peak
scan interval (min)
Specifies the MPPT multi-peak
scanning interval.
This parameter is displayed only
when MPPT multi-peak scanning
is set to Enable.
RCD enhancing
RCD refers to the residual current of
the SUN2000 to the ground. To
ensure device security and personal
safety, RCD should comply with the
standard. If an AC switch with a
residual current detection function is
installed outside the SUN2000, this
function should be enabled to reduce
the residual current generated during
SUN2000 running, thereby
preventing the AC switch from
misoperations.
N/A
Reactive power
output at night
In some specific application
scenarios, a power grid company
requires that the SUN2000 can
perform reactive power
compensation at night to ensure that
the power factor of the local power
grid meets requirements.
This parameter is configurable only
when Isolation is set to Input
ungrounded, with a transformer.
PID protection at
night
● When PID protection at night is
set to Enable, the SUN2000 will
shut down automatically if it
detects abnormality in PID voltage
compensation during the reactive
power compensation at night.
● When PID protection at night is
set to Disable, the SUN2000 will
operate in grid-tied mode if it
detects abnormality in PID voltage
compensation during the reactive
power compensation at night.
N/A
Power quality
optimization mode
If Power quality optimization mode
is set to Enable, the inverter output
current harmonics will be optimized.
N/A
SUN2000-(50KTL, 60KTL, 65KTL)-M0
User Manual