Parameter
Description
Remarks
HVRT compensation
power factor of
reactive power in
positive sequence
During HVRT, the inverter needs to
generate reactive power to support the
power grid. This parameter is used to
set the reactive power generated by
the inverter.
N/A
VRT exit hysteresis
threshold
Specifies the LVRT/HVRT recovery
threshold.
● This parameter is displayed
when LVRT or HVRT is set to
Enable.
● LVRT recovery threshold =
Threshold for triggering LVRT
+ VRT exit hysteresis threshold
● HVRT recovery threshold =
Threshold for triggering HVRT
+ VRT exit hysteresis threshold
Grid voltage
protection shield
during VRT
Specifies whether to shield the
undervoltage protection function
during LVRT or HVRT.
This parameter is displayed when
LVRT or HVRT is set to Enable.
Active islanding
Specifies whether to enable the active
islanding protection function.
N/A
Soft start time after
grid failure (s)
Specifies the time for the power to
gradually increase when the SUN2000
restarts after the power grid recovers.
N/A
7.2.2.4 Setting Power Adjustment Parameters
Procedure
Step 1 Choose Function Menu > Settings > Power Adjustment to access the settings
screen.
SUN2000-(50KTL, 60KTL, 65KTL)-M0
User Manual
7 Man-Machine Interactions
Issue 06 (2020-07-07)
Copyright © Huawei Technologies Co., Ltd.
90