SUN2000-(55KTL, 60KTL) Series
User Manual
7 Man-Machine Interactions
Issue 02 (2017-07-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
72
7.2.1.2 Setting Protection Parameters
Procedure
Step 1
Choose
Function Menu
>
Settings
>
Protection Parameters
to access the parameters
setting screen.
Figure 7-3
Protection parameter (advanced user)
----End
Parameter List
No.
Parameter
Description
Unit
Default
Value
Value Range
1
Insulation
resistance
protection
To ensure device safety, the
SUN2000 detects the
insulation resistance of the
input side to the ground when
it starts a self-check. If the
detected value is less than the
preset value, the SUN2000
does not start.
MΩ
0.05
[0.033, 1.5]