No. Parameter Description
Unit
Default
Value
Value Range
Remarks
personal safety, RCD
should comply with
the standard. If an AC
switch with a residual
current detection
function is installed
outside the SUN2000,
this function should be
enabled to reduce the
residual current
generated during
SUN2000 running,
thereby preventing the
AC switch from
misoperations.
4
Reactive
power
output at
night
In some specific
application scenarios,
a power grid company
requires that the
SUN2000 can perform
reactive power
compensation at night
to ensure that the
power factor of the
local power grid meets
requirements.
N/A
Disable
Disable
Enable
This parameter is
configurable only
when
Isolation
is
set to
Input
ungrounded, with
a transformer
.
5
Power
quality
optimizatio
n mode
If
Power quality
optimization mode
is
set to
Enable
, the
inverter output current
harmonics will be
optimized.
N/A
Disable
Disable
Enable
N/A
6
PV module
type
Specifies the type of
PV modules.
N/A
Crystalline
silicon
Crystalline
silicon
Film
CPV 1
CPV 2
If
PV module
type
is set to
Crystalline
silicon
or
Film
,
the SUN2000
will run properly
and will not shut
down if PV
modules are
shaded.
If
PV module
type
is set to
CPV 1
, the
SUN2000 can
restart quickly in
60 minutes if PV
modules are
shaded and the