7 Man-Machine Interactions
Issue 02 (2017-07-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
78
No. Parameter Description
Unit
Default
Value
Value Range
Remarks
a PV string is working
with high power.
19
String
detection
power
segment
division
percentage
Specifies the
thresholds for
determining whether a
PV string is working
with high power or
low power. This
parameter is used to
distinguish the
working status of PV
strings.
%
50
[1, 100]
20
String
detection
reference
asymmetric
coefficient
Specifies the threshold
for determining PV
string exception. The
false alarms caused by
fixed shadow shading
can be controlled by
changing this
parameter.
N/A
20
[5, 100]
This parameter is
displayed when
String monitor
is
set to
Enable
.
21
String
detection
starting
power
percentage
Specifies the threshold
for starting PV string
exception detection.
The false alarms
caused by fixed
shadow shading can
be controlled by
changing this
parameter.
%
20
[1, 100]
22
Shutdown
at 0%
power limit
If this parameter is set
to
Enable
, the
SUN2000 shuts down
after receiving the 0%
power limit command.
If this parameter is set
to
Disable
, the
SUN2000 does not
shut down after
receiving the 0%
power limit command.
N/A
Disable
Disable
Enable
N/A
23
Maximum
apparent
power
Specifies the output
upper threshold for the
maximum apparent
power to adapt to the
capacity requirements
for standard and
customized
transformers.
kW
Smax_limit
[Maximum
active power,
Smax_limit]
If the maximum
active power equals
Smax_limit, this
parameter is not
displayed.