SUN2000-(55KTL, 60KTL) Series
User Manual
7 Man-Machine Interactions
Issue 02 (2017-07-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
79
No. Parameter Description
Unit
Default
Value
Value Range
Remarks
24
Maximum
active
power
Specifies the output
upper threshold for the
maximum active
power to adapt to
various market
requirements.
kW
Pmax_limit
[0.1,
Pmax_limit]
N/A
25
Tracking
system
controller
Selects a controller
vendor.
N/A
N/A
N/A
N/A
26
Duration
for
determinin
g
short-time
grid
disconnecti
on
The standards of
certain countries and
regions require that
the SUN2000 should
not disconnect from
the power grid if the
power grid
experiences a
short-time failure. The
SUN2000 needs to
restart quickly after
the power grid
recovers.
ms
3000
[500, 20000]
N/A
27
Adjust
total
energy
yield
Specifies the initial
energy yield of the
SUN2000. This
parameter is used in
SUN2000 replacement
scenarios. Set the
initial energy yield of
the new SUN2000 to
the total energy yield
of the old SUN2000 to
ensure continuous
statistics of
cumulative energy
yield.
kWh
N/A
[0.00,
42949600.00]
N/A
28
DC input
detection
If
DC input detection
is set to
Disable
, the
SUN2000 does not
perform automatic DC
input detection or
manual DC output
detection.
N/A
Enable
Disable
Enable
N/A
29
Commande
d shutdown
hold after
power
recovery
The standards of
certain countries and
regions require that
the SUN2000 remains
in the commanded
N/A
The default
value varies
depending
on the grid
code. The
Disable
Enable
N/A