SUN2000-(55KTL, 60KTL) Series
User Manual
7 Man-Machine Interactions
Issue 02 (2017-07-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
81
Figure 7-5
Grid Parameters (special user)
----End
Parameter List
No.
Parameter
Description
Unit Default
Value
Value Range
Remarks
1
Grid code
Set this parameter
based on the grid code
of the country or
region where the
SUN2000 is used and
the SUN2000
application scenario.
N/A
The default
value varies
depending on
the model.
The
displayed
value
prevails.
N/A
N/A
2
Auto start upon
grid recovery
Specifies whether to
allow the SUN2000 to
automatically start
after the power grid
recovers.
N/A
The default
value varies
depending on
the grid code.
The
displayed
value
prevails.
Disable
Enable
N/A
3
Grid connection
duration after
power grid
recovery
Specifies the waiting
time for SUN2000
restart after the power
grid recovers.
s
[0, 900]
N/A
4
Grid
reconnection
voltage upper
limit
The standards of
certain countries and
regions require that the
SUN2000 must not
connect to the power
V
The default
value varies
depending on
the grid code.
The
[100%Vn,
136%Vn]
Vn
represents
the rated
voltage.