7 Man-Machine Interactions
Issue 02 (2017-07-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
82
No.
Parameter
Description
Unit Default
Value
Value Range
Remarks
grid when the power
grid voltage is higher
than the upper limit.
displayed
value
prevails.
5
Grid
reconnection
voltage lower
limit
The standards of
certain countries and
regions require that the
SUN2000 must not
connect to the power
grid when the power
grid voltage is lower
than the lower limit.
V
[45%Vn,
95%Vn]
6
Grid
reconnection
frequency
upper limit
The standards of
certain countries and
regions require that the
SUN2000 must not
connect to the power
grid when the power
grid frequency is
higher than the upper
limit.
Hz
The default
value varies
depending on
the grid code.
The
displayed
value
prevails.
[100%Fn,
112%Fn]
Fn represents
the rated
frequency.
7
Grid
reconnection
frequency
lower limit
The standards of
certain countries and
regions require that the
SUN2000 must not
connect to the power
grid when the power
grid frequency is lower
than the lower limit.
Hz
[85%Fn,
100%Fn]
8
Reactive power
compensation
(cosψ-P) trigger
voltage
Specifies the voltage
threshold for triggering
reactive power
compensation when
low voltage
ride-through (LVRT)
occurs.
%
The default
value varies
depending on
the grid code.
The
displayed
value
prevails.
[100, 110]
N/A
9
Reactive power
compensation
(cosψ-P) exit
voltage
Specifies the voltage
threshold for exiting
reactive power
compensation when the
SUN2000 recovers
from LVRT.
%
[90, 100]
N/A