SUN2000-(55KTL, 60KTL) Series
User Manual
7 Man-Machine Interactions
Issue 02 (2017-07-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
84
No.
Parameter
Description
Unit
Default
Value
Value Range
Remarks
3
10 minute OV
protection
Specifies the
10-minute
overvoltage
protection threshold.
V
The default
value varies
depending
on the grid
code. The
displayed
value
prevails.
[1 x Vn, 1.36 x Vn]
Vn
represents
the rated
voltage.
4
10 minute OV
protection time
Specifies the
10-minute
overvoltage
protection duration.
ms
[50, 7200000]
5
Level-1 OV
protection
Specifies the level-1
overvoltage
protection threshold.
V
The default
value varies
depending
on the grid
code. The
displayed
value
prevails.
[1 x Vn, 1.36 x Vn]
Vn
represents
the rated
voltage.
6
Level-1 OV
protection time
Specifies the level-1
overvoltage
protection duration.
ms
[50, 7200000]
7
Level-2 OV
protection
Specifies the level-2
overvoltage
protection threshold.
V
The default
value varies
depending
on the grid
code. The
displayed
value
prevails.
[1 x Vn, 1.36 x Vn]
Vn
represents
the rated
voltage.
8
Level-2 OV
protection time
Specifies the level-2
overvoltage
protection duration.
ms
[50, 7200000]
9
Level-1 UV
protection
Specifies the level-1
undervoltage
protection threshold.
V
The default
value varies
depending
on the grid
code. The
displayed
value
prevails.
[0.15 x Vn, 1 x Vn]
Vn
represents
the rated
voltage.
10
Level-1 UV
protection time
Specifies the level-1
undervoltage
protection duration.
ms
[50, 7200000]
11
Level-2 UV
protection
Specifies the level-2
undervoltage
protection threshold.
V
The default
value varies
depending
on the grid
code. The
displayed
value
prevails.
[0.15 x Vn, 1 x Vn]
Vn
represents
the rated
voltage.
12
Level-2 UV
protection time
Specifies the level-2
undervoltage
protection duration.
ms
[50, 7200000]
13
Level-1 OF
protection
Specifies the level-1
overfrequency
protection threshold.
Hz
The default
value varies
depending
on the grid
code. The
displayed
value
[1 x Fn, 1.15 x Fn]
Fn
represents
the rated
frequency.
14
Level-1 OF
protection time
Specifies the level-1
overfrequency
protection duration.
ms
[50, 7200000]