SUN2000-(55KTL, 60KTL) Series
User Manual
7 Man-Machine Interactions
Issue 02 (2017-07-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
85
No.
Parameter
Description
Unit
Default
Value
Value Range
Remarks
prevails.
15
Level-2 OF
protection
Specifies the level-2
overfrequency
protection threshold.
Hz
The default
value varies
depending
on the grid
code. The
displayed
value
prevails.
[1 x Fn, 1.15 x Fn]
Fn
represents
the rated
frequency.
16
Level-2 OF
protection time
Specifies the level-2
overfrequency
protection duration.
ms
[50, 7200000]
17
Level-1 UF
protection
Specifies the level-1
underfrequency
protection threshold.
Hz
The default
value varies
depending
on the grid
code. The
displayed
value
prevails.
[0.85 x Fn, 1 x Fn]
Fn
represents
the rated
frequency.
18
Level-1 UF
protection time
Specifies the level-1
underfrequency
protection duration.
ms
[50, 7200000]
19
Level-2 UF
protection
Specifies the level-2
underfrequency
protection threshold.
Hz
The default
value varies
depending
on the grid
code. The
displayed
value
prevails.
[0.85 x Fn, 1 x Fn]
Fn
represents
the rated
frequency.
20
Level-2 UF
protection time
Specifies the level-2
underfrequency
protection duration.
ms
[50, 7200000]
21
Level-3 OV
protection
Specifies the level-3
overvoltage
protection threshold.
V
The default
value varies
depending
on the grid
code. The
displayed
value
prevails.
[1 x Vn, 1.36 x Vn]
Vn
represents
the rated
voltage.
22
Level-3 OV
protection time
Specifies the level-3
overvoltage
protection duration.
ms
[50, 7200000]
23
Level-4 OV
protection
Specifies the level-4
overvoltage
protection threshold.
V
The default
value varies
depending
on the grid
code. The
displayed
value
prevails.
[1 x Vn, 1.36 x Vn]
Vn
represents
the rated
voltage.
24
Level-4 OV
protection time
Specifies the level-4
overvoltage
protection duration.
ms
[50, 7200000]
25
Level-3 UV
protection
Specifies the level-3
undervoltage
protection threshold.
V
The default
value varies
depending
on the grid
code. The
displayed
value
[0.15 x Vn, 1 x Vn]
Vn
represents
the rated
voltage.
26
Level-3 UV
protection time
Specifies the level-3
undervoltage
protection duration.
ms
[50, 7200000]