Parameter List
No.
Parameter
Description
Unit Default
Value
Value Range
Remarks
1
LVRT
When the power grid
voltage is abnormally
low for a short time,
the SUN2000 cannot
disconnect from the
power grid
immediately and has
to work for some time.
This is called LVRT.
N/A
The default
value varies
depending on
the grid code.
The displayed
value prevails.
Disable
Enable
N/A
2
LVRT threshold
Specifies the threshold
for triggering LVRT.
V
[50%Vn,
92%Vn]
N/A
3
LVRT
undervoltage
protection shield
Specifies whether to
shield the
undervoltage
protection function
during LVRT.
N/A
The default
value varies
depending on
the grid code.
The displayed
value prevails.
Disable
Enable
N/A
4
LVRT reactive
power
compensation
power factor
During LVRT, the
SUN2000 needs to
generate reactive
power to support the
power grid. This
parameter is used to
set the reactive power
generated by the
SUN2000.
N/A
[0, 3]
For
example, if
you set
LVRT
reactive
power
compensat
ion power
factor
to
2
,
the reactive
power
generated
by the
SUN2000
is 20% of
the rated
power
when the
AC voltage
drops by
10% during
LVRT.
5
High voltage
ride-through
When the power grid
voltage is abnormally
high for a short time,
the SUN2000 cannot
disconnect from the
power grid
immediately and has
to work for some time.
This is called high
N/A
The default
value varies
depending on
the grid code.
The displayed
value prevails.
Disable
Enable
N/A