SUN2000-(55KTL, 60KTL) Series
User Manual
7 Man-Machine Interactions
Issue 02 (2017-07-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
88
No.
Parameter
Description
Unit Default
Value
Value Range
Remarks
voltage ride-through
(HVRT).
6
Active islanding
Specifies whether to
enable the active
islanding protection
function.
N/A
Disable
Enable
N/A
7
Voltage rise
suppression
The standards of
certain countries and
regions require that
the active power of the
SUN2000 be derated
according to a certain
gradient when the
output voltage exceeds
a certain value.
N/A
The default
value varies
depending on
the grid code.
The displayed
value prevails.
Disable
Enable
N/A
8
Voltage rise
suppression
reactive
adjustment point
The standards of
certain countries and
regions require that
the SUN2000 must
generate a certain
amount of reactive
power when the
output voltage exceeds
a certain value.
%
[100, 115]
This
paramet
er is
displaye
d when
Voltage
rise
suppres
sion
is
set to
Enable
.
The
value of
Voltage
rise
suppres
sion
active
deratin
g point
must be
greater
than
that of
Voltage
rise
suppres
sion
reactiv
e
adjust
ment
point
.
9
Voltage rise
suppression active
derating point
The standards of
certain countries and
regions require that
the active power of the
SUN2000 be derated
according to a certain
gradient when the
output voltage exceeds
a certain value.
%
[100, 115]
10
Frequency change
The SUN2000 triggers N/A
The default
Disable
N/A