SUN2000-(55KTL, 60KTL) Series
User Manual
7 Man-Machine Interactions
Issue 02 (2017-07-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
89
No.
Parameter
Description
Unit Default
Value
Value Range
Remarks
rate protection
protection when the
power grid frequency
changes too fast.
value varies
depending on
the grid code.
The displayed
value prevails.
Enable
11
Frequency change
rate protection
point
Specifies the
frequency change rate
protection threshold.
Hz/s
[0.1, 2.5]
This
parameter
is
displayed if
Frequency
change
rate
protection
is set to
Enable
.
12
Frequency change
rate protection
time
Specifies the
frequency change rate
protection duration.
s
[0.2, 20.0]
13
Soft start time
after grid failure
Specifies the time for
the power to gradually
increase when the
SUN2000 restarts
after the power grid
recovers.
s
The default
value varies
depending on
the grid code.
The displayed
value prevails.
[20, 800]
N/A
7.2.2.4 Setting Power Adjustment Parameters
Procedure
Step 1
Choose
Function Menu
>
Settings
>
Power Adjustment
to access the parameters setting
screen.