Crimping the OT terminal
NO TICE
● Pay attention not to damage the core wire when stripping a cable.
● The cavity formed after the conductor crimp strip of the OT terminal is crimped
must wrap the core wires completely. The core wires must contact the OT
terminal closely.
● Wrap the wire crimping area with heat shrink tubing or PVC insulation tape.
The following figure uses heat shrink tubing as an example.
● When using the heat gun, protect devices from being scorched.
Figure 5-2 Crimping the OT Terminal
(1) Cable
(2) Core wire
(3) Heat shrink tubing
(4) OT terminal
(5) Hydraulic pliers
(6) Heat gun
SUN2000-(60KTL, 65KTL)-M0
User Manual (Mexico Edition)
5 Electrical Connections
Issue 06 (2020-10-12)
Copyright © Huawei Technologies Co., Ltd.
37