SUN2000-63KTL-JPH0
User Manual
5 Electrical Connections
Issue 04 (2019-06-30)
Copyright © Huawei Technologies Co., Ltd.
38
No.
Cable
Type
Conductor
Cross-Sectional
Area Range
Outer
Diameter
Source
3
AC output
power cable
(OT/DT
terminal)
If you connect a PE cable
to the PE point on the
enclosure, you are
advised to use a
three-core (U, V, and W)
outdoor copper cable and
M10 OT/DT terminals
(U, V, and W).
If you connect a PE cable
to the PE point in the
maintenance
compartment, you are
advised to use a four-core
(U, V, W, and PE)
outdoor copper cable,
M10 OT/DT terminals
(U, V, and W), and M8
OT/DT terminals (PE).
You do not need to
prepare a PE cable
separately.
U, V, and W:
22–95 mm
2
PE: ≥ 16 mm
2
.
For details, see
24–57 mm
Prepared
by the
customer
4
DC input power
cable
PV cable that meets the 1500
V standard
4–6 mm
2
(12–10
AWG)
4.5–7.8 mm
Prepared
by the
customer
The AC output power cable can be an aluminum alloy cable with a conductor cross-sectional
area of 35–95 mm
2
.
Table 5-3
PE cable specifications
Conductor Cross-Sectional Area S of the AC
Power Cable (mm
2
)
Conductor Cross-Sectional Area S
P
of the PE
Cable (mm
2
)
16 < S ≤ 35
S
P
≥ 16
35 < S
S
P
≥ S/2
The specifications are valid only if the conductors of the PE cable and AC power cable use the same material. If
the materials are different, ensure that the conductor cross-sectional area of the PE cable produces a
conductance equivalent to that of the cable specified in the table.