SUN2000-63KTL-JPH0
User Manual
7 Man-Machine Interactions
Issue 04 (2019-06-30)
Copyright © Huawei Technologies Co., Ltd.
79
Parameter
Description
Value Range (Vn: rated
voltage, Fn: rated frequency)
Level-N OV
protection (V)
Specifies the level-N grid overvoltage protection
threshold.
NOTE
N can be 1, 2, 3, or 4.
When
HVRT
is set to
Enable
and
Level-1 OV
protection
is higher than
HVRT triggering
threshold
, if the grid voltage is between
HVRT
triggering threshold
and
Level-1 OV protection
,
the SUN2000 could start and shut down repeatedly.
Level-1 OV protection: [1 x Vn,
1.25 x Vn]
Level-2, 3, and 4 OV
protection: [1 x Vn, 1.36 x Vn]
Level-N OV
protection time (ms)
Specifies the level-N grid overvoltage protection
duration.
NOTE
N can be 1, 2, 3, or 4.
[50, 7200000]
Level-N UV
protection (V)
Specifies the level-N grid undervoltage
protection threshold.
NOTE
N can be 1, 2, 3, or 4.
When
LVRT
is set to
Enable
and
Level-1 UV
protection
is lower than
LVRT threshold
, if the
grid voltage is between
Level-1 UV protection
and
LVRT threshold
, the SUN2000 could start
and shut down repeatedly.
[0.15 x Vn, 1 x Vn]
Level-N UV
protection time (ms)
Specifies the level-N grid undervoltage
protection duration.
NOTE
N can be 1, 2, 3, or 4.
[50, 7200000]
Level-N OF
protection (Hz)
Specifies the level-N grid overfrequency
protection threshold.
NOTE
N can be 1 or 2.
[1 x Fn, 1.15 x Fn]
Level-N OF
protection time (ms)
Specifies the level-N grid overfrequency
protection duration.
NOTE
N can be 1 or 2.
[50, 7200000]
Level-N UF
protection (Hz)
Specifies the level-N grid underfrequency
protection threshold.
NOTE
N can be 1 or 2.
[0.8 x Fn, 1 x Fn]
Level-N UF
protection time (ms)
Specifies the level-N grid underfrequency
protection duration.
NOTE
N can be 1 or 2.
[50, 7200000]