SUN2000-63KTL-JPH0
User Manual
7 Man-Machine Interactions
Issue 04 (2019-06-30)
Copyright © Huawei Technologies Co., Ltd.
80
----End
7.6.1.3 Setting Feature Parameters
Procedure
Step 1
Choose
Function Menu
>
Settings
>
Feature Parameters
to set feature parameters.
Figure 7-21
Feature parameters
Table 7-10
Feature parameters
Parameter
Description
Value Range (Vn: rated
voltage)
LVRT
When the power grid voltage is abnormally low
for a short time, the SUN2000 cannot disconnect
from the power grid immediately and has to work
for some time. This is called LVRT.
Disable
Enable
LVRT threshold (V)
Specifies the threshold for triggering LVRT.
[50%Vn, 100%Vn]
Grid voltage
protection shielding
during HVRT/LVRT
Specifies whether to shield the
undervoltage/overvoltage protection during
HVRT/LVRT.
Disable
Enable