TP48200A-HX09A2 & TBC300A-TCA2
Installation Guide
A Associations between Alarms and Dry Contacts on the
UIM
Issue 01 (2013-10-25)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
92
Port Type
Silk Screen
Associated Alarm
ALM6
Reports alarms for overhigh or over low battery
temperatures.
Default mode (Close: alarm; Open: normal) can
be modified as required.
ALM7
Reports battery cabinet alarms (for fan faults,
TEC faults, and door open)
Default mode (Close: alarm; Open: normal) can
be modified as required.
ALM8
Reports power cabinet fan faults or high
temperatures detected by the temperature control
unit (TCU) in the power cabinet.
Default mode (Close: alarm; Open: normal) can
be modified as required.