3 Diagnostics
Tecal RH5485 Server
Problem Determination and Service Guide
3-66
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Issue 02 (2011-05-25)
Numeric sensor Ambient
Temp going high (upper
critical) has deasserted.
Info
An upper critical sensor going
high has deasserted.
No action; information only.
Numeric sensor Ambient
Temp going high (upper
non-recoverable) has
deasserted.
Info
An upper non-recoverable sensor
going high has deasserted.
No action; information only.
Numeric sensor Planar 3.3V
going low (lower critical)
has asserted.
Error
A lower critical sensor going low
has asserted.
(Trained service technician only)
Replace the I/O-board shuttle.
Numeric sensor Planar 3.3V
going high (upper critical)
has asserted.
Error
An upper critical sensor going
high has asserted.
(Trained service technician only)
Replace the I/O-board shuttle.
Numeric sensor Planar 3.3V
going low (lower critical)
has deasserted.
Info
A lower critical sensor going low
has deasserted.
No action; information only.
Numeric sensor Planar 3.3V
going high (upper critical)
as deasserted.
Info
An upper critical sensor going
high has deasserted.
No action; information only.
Numeric sensor Planar 5V
going low
(lower critical) has asserted.
Error
A lower critical sensor going low
has asserted.
(Trained service technician only)
Replace the I/O-board shuttle.
Numeric sensor Planar 5V
going high
(upper critical) has asserted.
Error
An upper critical sensor going
high has asserted.
(Trained service technician only)
Replace the I/O-board shuttle.
Numeric sensor Planar 5V
going low
(lower critical) has
deasserted.
Info
A lower critical sensor going low
has deasserted.
No action; information only.
Numeric sensor Planar 5V
going high
(upper critical) has
deasserted.
Info
An upper critical sensor going
high has deasserted.
No action; information only.
Numeric sensor Planar 12V
going low
(lower critical) has asserted.
Error
A lower critical sensor going low
has asserted.
Check the OVER SPEC LED
(see the information about the
OVER SPEC LED in “Light path
diagnostics LEDs”).
Numeric sensor Planar 12V
going high (upper critical)
has asserted.
Error
An upper critical sensor going
high has asserted.
Check the OVER SPEC LED
(see the information about the
OVER SPEC LED in “Light path
diagnostics LEDs”).