TP48200A-DT19C1 & DT19C2 & HT19C1 & HT19C2
Installation Guide
2 Installation Preparations
Issue 03 (2014-02-23)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
13
Model
Dimensions (H x W x D)
Weight
Rectifier
R4850G2
40.8 mm x 105 mm x 281 mm
≤ 2 kg
R4830G2
≤ 1.8 kg
2.3 Installation Dimensions
shows the installation dimensions.
Figure 2-2
Installation dimensions
2.4 Requirements for Cable Routing
Cables should be more than 20 mm away from heat source components or area,
preventing direct damage (melting) to the insulation layer or functional degradation
(aging or broken).
The bending radius of cables should be greater than or equal to five times the diameter of
the cables.
Cables of the same type should be bound together. Cables of different types should keep
a minimum distance of 30 mm from each other to avoid tangles.
Cables that are bound together should be close to each other, neat, and free of damage.
The protection ground cables must not be bound to or tangled with the signal cables. An
appropriate distance should be left between them to minimize interruption.
AC power cables, DC power cables, signal cables, and communications cables must be
bound separately.