C Associations Between Alarms and Dry Contacts on the
UIM
Issue 07 (2019-11-15)
Copyright © Huawei Technologies Co., Ltd.
59
C
Associations Between Alarms and Dry
Contacts on the UIM
Table C-1
Associations between UIM02C dry contacts and alarms
Port Type
Silk
Screen
Name
Category
Associated Alarm
Dry contact
input ports
DIN1
-
-
Dry contact input 1 (open: normal;
closed: alarm)
DIN2
-
-
Dry contact input 2 (open: normal;
closed: alarm)
DIN3
-
-
Dry contact input 3 (open: normal;
closed: alarm)
DIN4
-
-
Dry contact input 4 (open: normal;
closed: alarm)
DIN5
-
-
Heater Fault (closed: normal; open:
alarm)
DIN6
-
-
Dry contact input 6 (open: normal;
closed: alarm)
Dry contact
output ports
The default
setting (closed:
normal; open:
alarm) can be
modified.
ALM1
Urgent alarm
System
incident
BLVD Warning/BLVD
Disconnected/Batt. Fuse Break/SMU
Fault/Batt Test Negative/Rectifier
Fault/DC Undervolt./DC Ultra
Undervolt.
ALM2
Not urgent alarm
System
incident
Insuff. Rdnt. Rects./Rectifier Fault/Fan
Fault/AC Ph. Failure
ALM3
System incident
AC
AC main
AC Ph. Failure/AC Failure/Long Mains
Failure
ALM4
–
–
Ret. Vent TS Fault/Fan Fault
ALM5
Rectifier incident
-
Rectifier Fault
ALM6
Battery incident
-
Batt. Fuse Break/Batt Test Negative