TP482000B V300R002C03 Telecom Power
(TP482000B-N20B1, TP482000B-N20B2,
TP481200B-N20B1, and TP481200B-N20B2)
User Manual
6 Routine Maintenance
Issue 07 (2020-04-10)
Copyright © Huawei Technologies Co., Ltd.
50
No.
Check Item
If...
Then...
because the ambient
temperature exceeds the
upper or lower threshold.
AC input over/undervoltage
protection has been
triggered.
The rectifier is in
hibernation.
4.
If the rectifier is in
hibernation, no action is
required.
Blinking:
The rectifier communication
has failed
The rectifier is faulty.
1.
Check that the rectifier
communications cable is
securely connected.
2.
Replace the rectifier.
3
Check the red indicator status
(normal: off).
Steady on:
The rectifier is latched off
due to output overvoltage.
The rectifier is faulty.
1.
Check that the cabinet is not
connected to an external DC
power source that has a
higher voltage.
2.
Check that the rectifier output
voltage is normal.
3.
Replace the rectifier.
6.4 SMU
Table 6-4
SMU maintenance checklist
No.
Check Item
If...
Then...
1
Check the green indicator status. Off:
There is no DC input.
The SMU is faulty.
1.
Check that the DC input
power cable is securely
connected.
2.
Check that the
communications cable is
securely connected.
3.
Replace the SMU.
2
Check the red indicator status.
Steady on:
A critical or major alarm has
been generated.
The SMU is faulty.
1.
Check components related to
the generated alarms.
2.
Replace the SMU.
3
Check the LCD screen status.
The LCD flat cable is loose.
The SMU is faulty.
1.
Check that the LCD flat cable
is securely connected.
2.
Replace the SMU.
4
Check that the SMU can
communicate with the NMS.
The communications cable
is loose.
Networking parameters are
not correctly set.
1.
Check that the
communications cable is
securely connected.
2.
Check that networking
parameter settings are correct.