TP482000B V300R002C03 Telecom Power
(TP482000B-N20B1, TP482000B-N20B2,
TP481200B-N20B1, and TP481200B-N20B2)
User Manual
7 Parts Replacement
Issue 07 (2020-04-10)
Copyright © Huawei Technologies Co., Ltd.
60
Figure 7-9
Installing an LCD
Step 6
Place the SMU cover in position and tighten the screws.
Step 7
Reconnect the cables to the RJ45 ports on the SMU based on the recorded information.
Step 8
Disconnect the ground cable for the ESD wrist strap, and take off the ESD wrist strap and
ESD gloves.
----End
7.2.3 Replacing the Button Board
Prerequisites
You have obtained an ESD wrist strap, a pair of ESD gloves, an ESD box or bag, a tool
kit, and the cabinet door key.
The new button board is intact.
Context
To replace the button board, you do not need to disconnect the AC input to the power system.
Procedure
Step 1
Connect the ground cable for the ESD wrist strap, and put on the ESD wrist strap and ESD
gloves.
Step 2
Record the positions of cables connected to RJ45 ports on the SMU, and disconnect the cables
from the ports.
Step 3
Remove the cover from the SMU.