TP482000B V300R002C03 Telecom Power
(TP482000B-N20B1, TP482000B-N20B2,
TP481200B-N20B1, and TP481200B-N20B2)
User Manual
7 Parts Replacement
Issue 07 (2020-04-10)
Copyright © Huawei Technologies Co., Ltd.
72
Figure 7-20
Short-circuiting a maintenance terminal
If the power distribution monitoring unit is not connected to the AC cabinet, skip
and
Step 3
Record the positions of cables connected to RJ45 ports on the power distribution monitoring
unit, and disconnect the cables from the ports.
Step 4
Unscrew and remove the cover from the power distribution monitoring unit, as shown in
Figure 1.
Step 5
Unscrew and remove the cover from the signal transfer board, as shown in
Use an M4 hex key to unscrew the cover of the signal transfer board.