3 Components
Issue 03 (2019-11-15)
Copyright © Huawei Technologies Co., Ltd.
22
Item
Specifications
AC input
One 3-pole 63 A AC input circuit breaker
AC output
Three 1-pole 16 A AC output circuit breaker (connected to the heater)
One 16 A maintenance socket with a residual current device (RCD)
Battery route
One 1-pole 100 A battery circuit breaker
DC output
BLVD: two 1-pole 50 A circuit breakers, two 1-pole 32 A circuit breakers, two
1-pole 16 A circuit breakers, two 1-pole 10 A circuit breakers, and one 1-pole 6 A
circuit breaker
LLVD: one 1-pole 32 A circuit breaker, one 1-pole 6 A circuit breaker, one 1-pole 16
A circuit breaker (connected to the TEC), and one 1-pole 6 A circuit breaker
SPD
AC SPD. Nominal lightning strike discharge current: 20 kA (8/20 µs); maximum
lightning strike discharge current: 40 kA (8/20 µs)
DC SPD. Differential mode: 10 kA (8/20 µs); common mode: 20 kA (8/20 µs)
3.2.1 Battery Switch
Figure 3-4
Battery switch
(1) Battery switch (behind the cover)
The battery switch is in the AUTO position by default before delivery and the system is
under automatic control.
Open the cover and flip the battery switch to MANUAL only when you need to connect
battery power supply manually. Remember to flip the battery switch back to AUTO after
the commissioning.
3.3 Rectifier
Rectifiers convert AC input into stable DC output.