TP48200A-HT15D3 Telecom Power (Russia, Megafon)
User Manual
3 Components
Issue 03 (2019-11-15)
Copyright © Huawei Technologies Co., Ltd.
23
Figure 3-5
Rectifier
(1) Run indicator
(2) Alarm indicator
(3) Fault indicator
(4) Locking latch
(5) Handle
Table 3-2
Rectifier indicator description
Indicator
Color
Status
Description
Run
indicator
Green
Steady on
The rectifier has an AC power input.
Off
The rectifier has no AC power input.
The rectifier is faulty.
Blinking at 0.5 Hz
The rectifier is being queried.
Blinking at 4 Hz
The rectifier is loading an application program.
Alarm
indicator
Yellow
Off
No alarm has been generated.
Steady on
The rectifier has generated an alarm due to ambient
overtemperature.
The rectifier has generated an alarm for shutdown due to
ambient overtemperature or undertemperature.
The rectifier is protecting itself against AC input overvoltage
or undervoltage.
The rectifier is hibernating.
Blinking at 0.5 Hz
The communication between the rectifier and the SMU has
been interrupted.
Fault
indicator
Red
Off
The rectifier is running properly.
Steady on
The rectifier has been locked out due to output overvoltage.
The rectifier has no output due to an internal fault.