TP48200E-H12C1 (Nepal, Ncell)
User Manual
3 Components
Issue 01 (2015-05-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
9
Indicator Description
Table 3-3
Indicator description
Indicator Color
Status
Description
Run
indicator
Green
Steady on
The rectifier provides output properly.
Off
The rectifier provides no output.
Alarm
indicator
Yellow
Off
No alarm is generated.
Steady on
The rectifier generates an alarm for power
limiting due to ambient overtemperature.
The rectifier generates an alarm for shutdown
due to ambient overtemperature or
undertemperature.
The rectifier protects against AC input
overvoltage or undervoltage.
The rectifier is hibernating.
Fault
indicator
Red
Off
The rectifier is running properly.
Steady on
The rectifier locks out due to output
overvoltage.
The rectifier has no output due to an internal
fault.
Blinking at 4 Hz The rectifier is loading an application program.
3.5 SMU02B
Appearance
Figure 3-7 shows an SMU02B.
Figure 3-7
SMU02B appearance