Silk
Screen
Signal Port
Pin Function
Remarks
JK1, JK2 Alarm digital
ports
The maximum voltage is 60 VDC and the
maximum load current is 500 mA.
l
When minor alarms are generated, JK2
is short-circuited.
l
When critical alarms are generated, JK1
is short-circuited.
l
Users can define alarm levels through
the BAM program.
Reserved
JKM1-
JKM4
Digital ports
The maximum voltage is 5.6 VDC and the
maximum current is 20 mA.
-
SIM1,
SIM2
Battery
unbalanced
sensor ports
l
Pin 1 is for the signal cable.
l
Pin 2 is reserved.
-
JAC1-
JAC6
Output ports of
the optical
coupler
Pin 1 and pin 2 are connected to pole C and
pole E of the optical coupler.
The optical coupling parameter Vce max is
40 VDC and Ic max is 80 mA. Avoid setting
the parameters to the maximum values.
Reserved
FU_AL
M
Detecting port
of the battery
fuse
l
Pin 1 is for the signal cable FU1+ and is
connected to the negative pole of the
battery.
l
Pin 2 is reserved for the FU1- signal.
-
JTD1-
JTD7
Input ports of
the standby
Boolean value
l
Pin 1 is for the +24 V power supply.
l
Pin 2 is for the +12 V power supply.
l
Pin 3 is for the signal cable.
l
Pin 4 is for grounding.
According to the actual requirements,
access related passive digital signals to pins
2 and pin 3.
Reserved
J1
DB50 port
The port connects the monitoring transfer
board and the monitoring board to input the
sensor signals and the output the control
signals.
-
NOTE
"JTD1-JTD7" are the input ports of the standby Boolean value. By default, the sensors are not configured.
You can determine the type of signal to be accessed. With related configuration, the monitor unit can
monitor them.
UA5000 Universal Access Unit
Environment Monitoring
7 EPS75-4815AF Monitoring Solution
Issue 01 (2012-08-17)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
95