Table 7-18
Connections of environment monitoring cables in the F01D1000 cabinet
Cable
One End Connects to...
The Other End Connects
to...
Monitoring cable
(2): EPS75-4815AF
(1): J1 port of the sensor
transfer box
Test and alarm cable
(3): STACK OUT port on
the HWCF transfer board
of the HABD shelf
l
(3.2): JTD1 port of the
sensor transfer box
l
(3.3-3.4): RS485/RS232
ports on the monitoring
unit of the
EPS75-4815AF
l
(3.1): STACK IN port on
the HWTF transfer
board of the HABF shelf
Test and alarm subtending cable (4): STACK OUT port on
the HWTF transfer board
of the HABF shelf
(5): JTD2 port of the sensor
transfer box
Monitoring cable of the surge
protector
Alarm terminal of the
surge protector
JTP3 port of the sensor
transfer box
Smoke sensor cable
Smoke sensor
JTP5 port of the sensor
transfer box
Monitoring cable of the heat
exchanger
Heat exchanger
JTP6 port of the sensor
transfer box
Test and alarm subtending cable (6): STACK OUT port on
the HABD shelf of the
right device compartment
(7): JTP7 port of the sensor
transfer box
Monitoring cable of the MDF
Alarm bar of the MDF
JTP1 port of the sensor
transfer box
Door status sensor
communication cable
Equipment compartment
and temperature control
compartment door status
sensor
JTM1 port of the sensor
transfer box
Monitoring cable of the
temperature and humidity sensor
Temperature and humidity
sensor
TEM-HU terminal of the
sensor transfer box
Monitoring cable of the battery
temperature sensor
Temperature sensor of the
battery
BAT_WE terminal of the
sensor transfer box
UA5000 Universal Access Unit
Environment Monitoring
7 EPS75-4815AF Monitoring Solution
Issue 01 (2012-08-17)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
106