Item
Data Plan for the
F01D500 Cabinet
Remarks
Power
distribution
parameters
AC overvoltage alarm
threshold of the power
supply: 280 V
This parameter is set according to the actual
requirements. When the AC voltage exceeds the
preset overvoltage alarm threshold, the system
reports an AC overvoltage alarm. In this case, the
rectifier unit powers off automatically to protect
the system.
Default: 280 V.
AC undervoltage alarm
threshold of the power
supply: 180 V
This parameter is set according to the actual
requirements. When the AC voltage falls below
the preset undervoltage alarm threshold, the
system reports an AC undervoltage alarm. In this
case, the rectifier unit powers off automatically to
protect the system.
Default: 180 V.
DC overvoltage alarm
threshold of the power
supply: 58 V
This parameter is set according to the actual
requirements. When the DC voltage exceeds the
preset overvoltage alarm threshold, the system
reports a DC overvoltage alarm. In this case, the
rectifier unit powers off automatically to protect
the system.
Default: 58 V.
DC undervoltage alarm
threshold of the power
supply: 45 V
This parameter is set according to the actual
requirements. When the DC voltage falls below
the preset undervoltage alarm threshold, the
system reports a DC undervoltage alarm. In this
case, the rectifier unit powers off automatically to
protect the system.
Default: 45 V.
Battery test
parameters
Battery auto-discharging
test: auto-test
-
Power-off auto-test:
forbid
This parameter is set according to the actual
requirements.
Default: permit.
Timed auto-test: permit
This parameter is set according to the actual
requirements.
Default: forbid.
Battery auto-discharging
test period: 180d
This parameter is set according to the actual
requirements.
Default: 120d.