Table 7-21
Commands for configuring the EPS75-4815AF
To...
Run the Command...
Add an EMU
emu add
Configure the battery charging
parameters
power charge
Configure the battery
management parameters and the
temperature compensation
parameters of the battery.
power battery
Configure the power supply load
power-off and battery set power-
off parameters
power off
Configure the power distribution
parameters
power supply-parameter
Configure the battery
discharging test parameters
power battery-test
Configure the rectifier unit
parameter
power module-num
Configure the load and battery
high-temperature power-off
parameters
power temperature-off
Configure the environment
monitoring parameters
power environment
Configure the external extended
digital parameters
power outside-digital
IDs of user-defined alarms in the digital parameters: IDs
1-20 are reserved alarm IDs in the system (1: AC_voltage;
2: AC_switch; 3: Battery_voltage; 4: Battery_fuse; 5:
Load_fuse; 6: Rectifier; 7: DC_power; 8: Cupboard_door;
9: Room_door; 10: Window; 11: Theft; 12: Wiring; 13:
Fan; 14: Fire; 15: Fog; 16: Water; 17: Diesel; 18: Smell
19: Air_conditioner; 20: SPD), and IDs 21-52 are alarm
IDs allocated to other user-defined alarms by users.
Query the configuration
parameters of the power system
display power system parameter
The following considers the configuration in the F01D500 cabinet as an example to describe the
process of configuring the environment monitoring parameters of the EPS75-4815AF.
1.
Log in to the PVM through the maintenance terminal and add an EMU.
huawei(config)#
emu add 0 POWER4875L 0 0 RS232 POWER4875L
UA5000 Universal Access Unit
Environment Monitoring
7 EPS75-4815AF Monitoring Solution
Issue 01 (2012-08-17)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
116