2.
Query the status of the EPS75-4815AF.
huawei(config)#
display emu 0
--------------------------------------------------------------------
EMU name : POWER4875L
EMU type : Pwr4875
EMU state : Normal
Frame ID : 0
Subnode : 0
COM Port : RS232
--------------------------------------------------------------------
3.
Enter the environment monitoring configuration mode and query the default configuration.
huawei(config)#
interface emu 0
huawei(config-if-power4875l-0)#
display power system parameter
EMU ID: 0 Power system information
----------------------------------------------------------------------------
charge control state : automatic control
equalizing Voltage : 56.500V floating Voltage: 53.500V
charge lmt quotiety: 0.150 equalizing time : 60 days
battery number : 1
battery 0 capacity : 65 AH
battery temperature test upper : 80C battery temperature test lower: -20C
temperature redeem quotiety : 80mV
battery temperature alarm upper: 50C battery temperature alarm lower: 0C
load off permit : forbid load off voltage : 44.000V
battery off permit : permit battery off voltage : 43.000V
AC over alarm voltage : 280V AC lack alarm voltage : 180V
DC over alarm voltage : 58 V DC lack alarm voltage : 45V
power module number: 5
module 0 address: 1 module 0 switch state : On
module 1 address: 2 module 1 switch state : On
module 2 address: 3 module 2 switch state : On
module 3 address: 4 module 3 switch state : On
module 4 address: 5 module 4 switch state : On
Load high-temperature-off permit: forbid
Load high-temperature-off temperature(C): 65
Battery high-temperature-off permit: forbid
Battery high-temperature-off temperature(C): 53
----------------------------------------------------------------------------
huawei(config-if-power4875l-0)#
display power environment parameter
EMU ID: 2 Power environment configration
parameter
----------------------------------------------------------------------------
AnalogID Name AlmUpper AlmLower TestUpper TestLower Unit
Type
0 Temperature 50 0 80 -20 C
Current
1 Humidity 80 10 100 0 %R.H.
Current
----------------------------------------------------------------------------
DigitalID Name Level |DigitalID Name
Level
0 - 1 | 1 -
1
2 - 1 | 3 -
1
4 - 1 | 5 -
1
6 -
1
----------------------------------------------------------------------------
The results show that the power, temperature, and humidity parameters have been
configured automatically in the system; however, certain parameters need to be modified,
and certain extended monitoring parameters need to be added.
4.
Configure the battery charging parameters.
UA5000 Universal Access Unit
Environment Monitoring
7 EPS75-4815AF Monitoring Solution
Issue 01 (2012-08-17)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
117