battery temperature alarm upper: 50C battery temperature alarm lower: 0C
load off permit : forbid load off voltage : 44.000V
battery off permit : permit battery off voltage : 43.000V
AC over alarm voltage : 280V AC lack alarm voltage : 180V
DC over alarm voltage : 58 V DC lack alarm voltage : 45V
power module number: 2
module 0 address: 1 module 0 switch state : On
module 1 address: 2 module 1 switch state : On
Load high-temperature-off permit: forbid
Load high-temperature-off temperature(C): 70
Battery high-temperature-off permit: permit
Battery high-temperature-off temperature(C): 53
----------------------------------------------------------------------------
huawei(config-if-power4875l-0)#
display power environment parameter
EMU ID: 2 Power environment configration
parameter
----------------------------------------------------------------------------
AnalogID Name AlmUpper AlmLower TestUpper TestLower Unit
Type
0 Temperature 68 -5 80 -20 C
Current
1 Humidity 80 10 100 0 %R.H.
Current
----------------------------------------------------------------------------
DigitalID Name Level |DigitalID Name
Level
0 Fan 0 | 1 HABF_FAN
0
2 - 0 | 3 SPD
1
4 Smoke 1 | 5 HEX
0
6 MDF-door
0
----------------------------------------------------------------------------
15. Query the alarms, and confirm that the door status alarm other than alarms for other
monitoring parameters is generated.
huawei(config-if-power4875l-0)#
display power alarm
EMU ID: 0 Power alarm information
----------------------------------------------------------------------------
Mains supply yes : Yes Mains supply lack : Normal
Total Vol lack : Normal
Load fuse 0 : Connect Second fuse : Connect
Load off : On Battery off : On
Battery 0 loop : Disconnect
Environment Temperature : Normal Environment Humidity : Normal
Door alarm : Alarm Water alarm : Normal
Fog alarm : Normal Wiring alarm : Normal
Module 0 : Normal
Module 1 : Normal
Module 2 : Normal
Battery temperature off state : Normal Load temperature off state : Normal
----------------------------------------------------------------------------
Name State |Name State
Spare Dig0(Fan) Normal|Spare(HABF_FAN)
Normal
Spare Dig2 Normal|Spare Dig3(SPD)
Normal
Spare Dig4(Smoke) Normal|Spare Dig5(HEX) Alarm
Spare Dig6(MDF-door) Alarm
----------------------------------------------------------------------------
UA5000 Universal Access Unit
Environment Monitoring
7 EPS75-4815AF Monitoring Solution
Issue 01 (2012-08-17)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
119